ATS22D62S6U
soft starter-ATS22-control110V-power 208V(15hp)/230V(20hp)/460V(40hp)/575V(50hp)
Range: Soft Start - Altistart 22 FAQ Documents & Downloads-
Product availability :
Stock - Normally stocked in distribution facility
-
Characteristics
Main range of product Altistart 22product or component type Soft starterproduct destination Asynchronous motorsproduct specific application Pumps and fanscomponent name ATS22Phase 3 phases[Us] rated supply voltage 208...600 V - 15...10 %motor power hp 15 hp 208 V20 hp 230 V40 hp 460 V50 hp 575 Vfactory setting current 52 Apower dissipation in W 59 W for standard applicationsutilisation category AC-53Atype of start Start with torque control (current limited to 3.5 In)IcL starter rating 62 A connection in the motor supply line for standard applicationsIP degree of protection IP20Complementary assembly style With heat sinkfunction available Internal bypasssupply voltage limits 177...660 Vsupply frequency 50...60 Hz - 10...10 %network frequency 45...66 Hzdevice connection In the motor supply line[Uc] control circuit voltage 110 V -15...10 % 50/60 Hzcontrol circuit consumption 20 Wdiscrete output number 2discrete output type Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/ORelay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/Ominimum switching current 100 mA 12 V DC relay outputsmaximum switching current 5 A 250 V AC resistive 1 relay outputs5 A 30 V DC resistive 1 relay outputs2 A 250 V AC inductive 0.4 20 ms relay outputs2 A 30 V DC inductive 7 ms relay outputsdiscrete input number 3discrete input type Logic LI1, LI2, LI3 5 mA 20 kOhmdiscrete input voltage 110 V <= 121 Vdiscrete input logic Positive logic LI1, LI2, LI3 < 20 V and <= 15 mA > 79 V <= 2 mAoutput current 0.4...1 Icl adjustablePTC probe input 750 Ohmcommunication port protocol Modbusconnector type 1 RJ45communication data link Serialphysical interface RS485 multidroptransmission rate 4800, 9600 or 19200 bpsinstalled device 31protection type Phase failure lineThermal protection starterThermal protection motormarking CEtype of cooling Forced convectionoperating position Vertical +/- 10 degreeheight 11.61 in (295 mm)width 5.71 in (145 mm)depth 8.15 in (207 mm)product weight 26.46 lb(US) (12 kg)Environment electromagnetic compatibility Conducted and radiated emissions level A IEC 60947-4-2Damped oscillating waves level 3 IEC 61000-4-12Electrostatic discharge level 3 IEC 61000-4-2Immunity to electrical transients level 4 IEC 61000-4-4Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3Voltage/current impulse level 3 IEC 61000-4-5standards EN/IEC 60947-4-2product certifications GOSTC-TickCCCCSAULvibration resistance 1.5 mm 2...13 Hz EN/IEC 60068-2-61 gn 13...200 Hz EN/IEC 60068-2-6shock resistance 15 gn 11 ms EN/IEC 60068-2-27noise level 45 dBpollution degree Level 2 IEC 60664-1relative humidity 0...95 % without condensation or dripping water EN/IEC 60068-2-3ambient air temperature for operation 14...104 °F (-10...40 °C) without derating> 104...< 140 °F (> 40...< 60 °C) with current derating 2.2 % per °Cambient air temperature for storage -13...158 °F (-25...70 °C)operating altitude <= 3280.84 ft (1000 m) without derating> 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 mOrdering and shipping details Category 22576 - ATS22 ALTISTARTDiscount Schedule CP1GGTIN 00785901692287Nbr. of units in pkg. 1Package weight(Lbs) 18.420000000000002Returnability YCountry of origin IDOffer Sustainability Sustainable offer status Green Premium productRoHS (date code: YYWW) Compliant - since 0939 - Schneider Electric declaration of conformity Schneider Electric declaration of conformityREACh Product environmental profile AvailableProduct Environmental ProfileProduct end of life instructions AvailableEnd of life manualContractual warranty Warranty period 18 months -
Documents and Downloads (11)
-
Dimensions Drawings
Frame Size BDimensions -
Mounting and Clearance
PrecautionsStandardsThe Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.
For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
ATS22 soft starters are open devices and must be mounted in a suitable enclosure.
Failure to follow these instructions will result in death or serious injury.
Air CirculationLeave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.
OverheatingTo avoid the soft starter to overheat, respect the following recommendations:
Mount the Altistart 22 Soft Starter within ± 10° of vertical.
Do not locate the Altistart 22 Soft Starter near heat radiating elements.
Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient temperature around the soft starter.
If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the bottom soft starter can adversely affect the ambient temperature around the top soft starter.
MountingConnection Between the Fan and the Altistart 22 Soft Starter1Altistart 22 Soft Starter2FanWall mounted or Floor-standing Enclosure with IP 23 Degree of protectionIntroductionTo help proper air circulation in the soft starter, grilles and forced ventilation can be installed.
Ventilation GrillesForced Ventilation Unit -
Connections and Schema
Power TerminalCage Style1Ground connectionPower connections, minimum and maximum wiring capabilities, tightening torqueIEC cable
UL cable
Power supply and output to motor
Size/gauge
min
4 mm (a)
10 AWG (a)
max
50 mm
1/0 AWG
Tightening torque
min
8 N.m
70 lb.in
max
8 N.m
70 lb.in
Strip length
15 mm
0.6 in.
Power connections, minimum required wiring sectionIEC cable
mm² (Cu 70°C/158°F) (1)
UL cable
AWG (Cu 75°C/167°F) (1)
16
4
110 Vac control, Logic Inputs (LI) 110 Vac, 3-wire control110 Vac control, Logic Inputs (LI) 110 Vac, 2-wire control, freewheelstop -
Performance Curves
Motor Thermal Protection - Cold CurvesCurvesAClass 10BClass 20CClass 30Trip time for a Standard Application (Class 10)3.5 ln
32 s
Trip time for a Severe Application (Class 20)3.5 ln
63 s
Trip time for a Severe Application (Class 30)3.5 ln
95 s
Motor Thermal Protection - Warm CurvesCurvesAClass 10BClass 20CClass 30Trip time for a Standard Application (Class 10)3.5 ln
16 s
Trip time for a Severe Application (Class 20)3.5 ln
32 s
Trip time for a Severe Application (Class 30)3.5 ln
48 s